EDC Building | Virtual Meters | Energy Use

Energy Use
Potential savings = / / %

Energy Use

The Energy Use chart compares the energy use under the existing state of operations (As-is) and the proposed energy use under optimal and fault-free operations (Corrected). This comparison can be used to assess the effects and magnitude of addressing HVAC faults and prioritize fault-correction efforts that most impact energy use. Energy use is disaggregated into three main end-uses: system-level heating, zone-level heating, and system-level cooling energy use. Focus fault-correction efforts to end-uses with greater energy Savings Potential.

Excessive system-level heating energy use may stem from deficiencies in the sequences of operation (i.e., soft fault) and/or mechanical faults with the heating coil valve or dampers (i.e., hard fault).
For example, a non-functional or absence of a supply air temperature reset policy may lead to increased operating time in an AHU's economizer mode during the heating season - increased outdoor air intake may lead to higher heating energy use. Inappropriate or lack of a weekly AHU schedule may lead to the AHU operating outside typical occupied hours, resulting in unnecessary and excessive heating energy use.
A faulty heating coil valve or heating coil may also result in excessive heating energy use. Leaks, resulting in reduced heating efficiency, may lead to increased heating energy use. An uncalibrated mixing box damper which may lead to unintentionally higher outdoor air intake would also result in higher energy use.
Example Outdoor Air Ratio chart with too little outdoor air.
No/Deficient SAT reset policy ❌

May cause excess economizer operation.

Recommendations: Ensure an appropriate SAT reset policy is operational - implement if one does not exist.

Example of deficient Mode of Operation chart
No/Deficient weekly schedule ❌

May cause excess operating time.

Recommendations: Ensure a weekly schedule is operational - implement if one does not exist.

Example Outdoor Air Ratio plot with too much outdoor air.
Leaking heating coil or valve ❌

May cause inefficient heating.

Recommendations: Check coil, valves, and surrounding pipework for leaks.

Example Outdoor Air Ratio chart with just right outdoor air.
Broken/uncalibrated outdoor air damper ❌

May cause excess outdoor air intake.

Recommendations: Check mixing box dampers for stuck open dampers and leaks.

Excessive zone-level heating energy use may stem from...

We're working on this! Please check back later.